3.4.2 Configuring PROFINET Fieldbus Adapter using Step7 Overview
This is an example of how to configure the PROFINET Fieldbus Adapter using Step7.
Configuring PROFINET Fieldbus Adapter
Use this procedure to configure the PROFINET Fieldbus Adapter using Siemens Step7.
The example uses a static IP address and no gateway. 3.4.2配置使用的Step7 PROFINET现场总线适配器 概观
这是如何使用配置PROFINET现场总线适配器的例子STEP7 。 配置PROFINET现场总线适配器
使用此过程配置使用西门子的PROFINET现场总线适配器STEP7 。 该示例使用静态IP地址,没有网关。 Action
Start Siemens Simatic Manager. On the PLC menu, click Edit Ethernet Node. 1 Click Browse. 2Note
3The PROFINET Fieldbus Adapter must already be configured in the IRC5 controller. Select the PROFINET Fieldbus Adapter to configure and click OK. Tip
Select a device in the list and click Flash. The LED on the selected device will flash repeatedly until Stop Flash is clicked. Action
4 Select Use IP parameters and enter the IP address and subnet mask and then click Assign IP configuration.-
Enter device name in the Device name text box and click Assign name. For more information about the other settings, see Siemens documentation. Note
5 The IP address and device name must be unique on the fieldbus network. Click Close.
6 Open the project to which the PROFINET Fieldbus Adapter should be added. 7 Open HW Config for the selected master. 8 On the Option menu, click Install GSD File.
The GSDML file for PROFINET Fieldbus Adapter must be imported from the RobotWare DVD.
9 In the Install GSD Files menu, select from the directory and click Browse.
10 Select the GSDML file from the RobotWare DVD and click Install. Click Yes to confirm the warning.
11 Click OK to complete the installation. 12 Click Close.
13 In the device list on the right-hand side of the HW Config, expand PROFINET IO\\Ad- ditional Field Devices\\General\\Fieldbus Adapter and select DSQC688. 14 Drag the DSQC688 device to the fieldbus network.
15 Expand the DI/DO folder for the DSQC688 device in the tree structure. Action
16 Select the DSQC688 icon added to the fieldbus network. 16
17 Drag the correct input size to slot 1and the correct output size to slot 2. 17
The input size shall be the same as the output size configured in the IRC5 controller. The output size shall be the same as the input size configured in the IRC5 controller. Note
Inputs and outputs must be added to the correct slots, otherwise the communication with the unit will not work properly.
If another size, then 64 byte input and 64 byte output are used, the size must be changed in the UNIT TYPE in the IRC5 controller configuration. 18 Right-click on the DSQC688 icon and select Object Properties. 18
19 Enter the same device name and IP address as when naming the device in step 4. 19 Click Ethernet to enter the IP address and make sure that Assign IP address via IO controller is selected. 20 Click OK. 20
21 On the Station menu, click Save and Compile. 21 22 On the PLC menu, click Download. 22 行动
1点击浏览。启动西门子SIMATIC管理器。在PLC菜单中,单击编辑以太网节点。 2注意 该PROFINET现场总线适配器必须已经在IRC5控制器进行配置。 3选择PROFINET现场总线适配器配置,然后单击确定。 尖
在列表中选择一个设备,然后单击闪存。所选择的设备上的指示灯会闪烁 直至停止闪光被点击。
4 选择使用IP参数,并输入IP地址和子网掩码,然后单击 分配IP配置。
在设备名称文本框中输入设备名称,然后单击分配名称。 有关其他设置的详细信息,请参阅西门子文档。 注意
5 该IP地址和设备名称必须是现场总线网络上是唯一的。 单击关闭。
6 打开该PROFINET现场总线适配器应加入该项目。 7打开HW Config中为所选主。
8在选项菜单中,单击安装GSD文件。
该GSDML文件PROFINET现场总线适配器必须从的RobotWare进口 DVD 。
9在安装GSD文件菜单中,从目录中选择,然后点击浏览。
10从DVD的RobotWare的GSDML文件,然后单击安装。单击Yes确认 警告。
11单击确定完成安装。 12单击关闭。
13在对硬件配置的右侧设备列表中,展开PROFINET IO \\ AD- ditional现场设备\\常规\\现场总线适配器,并选择DSQC688 。
14拖动DSQC688设备到现场总线网络。
15展开DI / DO夹用于在树结构中的DSQC688设备。 16选择添加到现场总线网络的DSQC688图标。 16
17拖动正确的输入大小插槽1和正确的输出尺寸插槽2 17 输入尺寸应是相同的构造,在IRC5控制器的输出大小。 输出尺寸应是相同的构造,在IRC5控制器的输入大小。 注意
输入和输出必须被添加到正确的插槽,否则该通信 与本机将无法正常工作。
如果另一个尺寸,然后64字节的输入和64字节的输出被使用的,大小必须 在IRC5控制器配置的单位类型改变。
18 在DSQC688图标18右键单击并选择对象属性。 18
19输入相同的设备名称和IP地址在第4步19命名的设备时, 点击以太网输入IP地址,并确保通过IO分配IP地址 选择控制器。 20单击确定。 20
21在站菜单上,单击保存和编译。 21 22在PLC菜单中,单击下载。