MODULE15
MECHANICAL, PLUMBING& E L E C T R I C A LInternationalDesign Standards
J A N U A R Y 2 0 0 5
Module - 15
Marriott - International
Mechanical, Plumbing & Electrical
A.Mechanical Systems........................................15AB.Plumbing Systems...........................................15BC.Electrical Systems...........................................15C
Module Organization
?This Module is a part of an integrated series of 17 Modules.?Coordination with information from other Modules is required.
?The symbol
additional information.
Marriott Confidential and Proprietary InformationThe contents of the Design Standards are confidential and proprietary to Marriott International, Inc. and may not bereproduced, disclosed, distributed or used without the express permission of an authorized representative of Marriott.
Copyright, Marriott International, Inc., unpublished material. All rights reserved.
Contents
January 2005Design Standards - Copyright, Marriott International, Inc.
Marriott Hotel - International
Mechanical - 15A
Module 15 - Part A
Mechanical Systems
Design Standards - Copyright, Marriott International, Inc. January 2005 15A - A
15A - Mechanical
Marriott Hotel - International
Mechanical Systems Table of Contents
Subject...................................................................................Page A. General Requirements.............................................................1 B. Building Cooling / Heating Load Calculations..........................2 C. HVAC System Requirements...................................................3 D. Central Cooling Plant...............................................................5 E. Central Heating Plant...............................................................8 F. Piping Systems......................................................................10 G. Air Side Systems....................................................................13 H. Public and Back-of-House AHUs...........................................16 I. Guestroom / Guest Corridor Fresh-Air AHUs........................18 J. Ductwork................................................................................20 K. Smoke Control System..........................................................23 L. Fuel Oil System......................................................................25 M. Testing and Balancing Services.............................................26 N. Automatic Temperature Controls (ATC) & Building
Management System (BMS)..................................................26 O. Table 15A-1 – Environmental Requirements.........................29
Module Organization
? This Module is a part of an integrated series of 17 Modules. ? Coordination with information from other Modules is required.
? The reference symbol
Marriott Confidential and Proprietary Information The contents of the Design Standards are confidential and proprietary to Marriott International, Inc. and may not be reproduced, disclosed, distributed or used without the express permission of an authorized representative of Marriott.
Copyright, Marriott International, Inc., unpublished material. All rights Reserved
15A - B
January 2005
Design Standards - Copyright, Marriott International, Inc.
Marriott Hotel - International
Mechanical Systems
Mechanical - 15A
A. General Requirements
1. Codes and Standards:
? Information contained in this Module is intended to set
minimum mechanical system requirements and is not intended to provide complete design solutions to project specific situations.
? Comply with the more stringent of governing laws,
applicable governing codes and regulations, and these Design Standards.
? Refer enhancements, deviations, and conflicts between
design standards to Marriott A&C Engineering for resolution.
? FM Global: Fired pressure vessels, boilers, boiler tanks
and their safety trains (controls that include combustion safeguards, safety shut-off valves, over temperature protection and pressure relief valves) are required to be FM Global approved.
2. Building Pressures: Design building to maintain positive
pressure, maintain environmental requirements (temperature and humidity) and ensure guest comfort.
? Minimum outside air intake quantities must exceed
building exhaust quantities by 10%.
? In high-rise buildings, consider \
and the resulting infiltration. The use of entry vestibules, with two sets of double doors will significantly reduce stack effect. See Module <2A> for application of architectural requirements at Lobby entrance.
3. Equipment Selection: Select and provide equipment,
components and specified materials rated for applicable service, environment, temperatures and pressures.
? Install interior designed equipment for inside use only
and not for outside use.
? Design and construct outside equipment for project
specific conditions.
4. Fire Protection / Life Safety: See Module <14>.
5. Environmental Requirements: Design and select
equipment to maintain indoor space temperature and humidity conditions when using ventilation requirements for occupants and internal heat gain in compliance with Table 15A-1 – HVAC Environmental Requirements at end of this document.
6. Dimensions, Sizes and Measurements: In this Standard,
conversions from English to metric (SI) units are approximate. Verify, coordinate and confirm product and material dimensions for required design applications.
Design Standards - Copyright, Marriott International, Inc.
January 2005
15A - 1