Control and monitoring functions available at each Manual Release Box: 在每一个人工释放的控制盒中控制和喷头灭火的功能
? Foam monitor start (open valve) 泡沫喷头启动(打开阀门)
? Foam monitor stop (System Reset) 泡沫喷头停止(系统重置)
? Foam monitor valve opened indication 泡沫喷头阀门打开指示
? Control and monitoring functions available at the Remote Control Panel : 在遥控控制面板上控制和灭火喷头的功能 ? Foam monitor 1 Operate system (release) 泡沫喷头1号操纵系统(释放)
? Foam monitor 2 Operate system (release) 泡沫喷头2操纵系统(释放)
? Foam monitor 3 Operate system (release) 泡沫喷头3操纵系统(释放) ? Foam Pump start 泡沫水泵启动 ? Foam pump stop 泡沫水泵停止 ? System reset 系统重置
? Foam monitor 1 valve opened indication 泡沫灭火喷头1号阀门打开指示
? Foam monitor 2 valve opened indication 泡沫灭火喷头2阀门打开指示
? Foam monitor 3 valve opened indication 泡沫灭火喷头3阀门打开指示 ? Foam Pump running indication 泡沫水泵的运行情况指示
Interface with the F&G system 与F&G系统的交融
The Foam Main Control Panel is connected to the F&G system and the foam fire fighting system status is indicated on the F&G workstation. When the Foam release PB is pressed in the Helideck Foam monitors, it gives signal to the Main Control Panel for Foam release. Simultaneously, signal is also sent to F&G system Panel to start Fire Water Pump. So, the Fire water Pump would be started whenever the Foam monitor is operated from the Foam platform PB. 泡沫朱控制面板与F&G系统连接,泡沫灭火系统的工作状态在F&G和工作站中显示。当泡沫释放PB加压到直升机机坪的喷头,系统就给主控制面板输送泡沫释放的信号。同时,信号同样被传输到F&G系统控制面板,启动消防水泵。消防水泵开启,从泡沫平台PB的泡沫喷头,无论什么时候工作。
The signals sent to the F&G system are: 传输到F&G系统的信号是
? Foam Pump Running 泡沫泵的运行
? Foam Pump Tripped 泡沫泵的运行状态
? System Power Supply Available 系统的电力供给
? Foam line valve opened 泡沫管线阀门的开启 ? Water line valve opened
5
Page 6 of 31
水管线阀门的开启
? Foam monitor 1 valve Opened 泡沫喷头1号阀门的开启
? Foam monitor 2 valve Opened 泡沫喷头2号阀门的开启
? Foam monitor 3 valve Opened 泡沫喷头3号阀门的开启 Fire water Pump start
3.3.2 Combined Foam/ Dry Powder System 泡沫和干粉组合系统
Two combined foam / dry powder fire fighting units are installed for the purpose of extinguishing minor fires. Hoses with nozzles are installed at the port forward and starboard forward foam monitors . Each set is equipped with 2 hoses and nozzles. The hoses and nozzles of the foam and powder system are connected with each other by a metal frame which can be hung around the operators neck by a strap. For proper operation all hose on the reel will need to be flaked out.
两组泡沫和干粉组合系统的消防灭火设备安装的目的在于针对轻度火灾的扑灭。带有喷头的消防管线安装在出口的前,启动面板朝向泡沫喷头。每一套带有两个管线和喷头。泡沫、干粉的管线和喷头利用金属结构连接在一起,可以利用带子挂在使用者的肩膀上。为了正确使用,所有的管线盘卷起来,并防止老化。 Storage tanks are located below the helpdesk containing 250 litres of foam concentrate and 250 kgs of powder..
储存灌位于直升机机坪下面,存量为250升泡沫和250公斤的干粉。
3.3.3 Fireman’s equipment and emergency equipment to be kept in the vicinity of the helideck. (min requirements).
消防人员的设备和应急设备存放在直升机机坪的附件(最低设备要求)
- 2 Fire suits ( complete with boots, helmets, gloves) 2套消防服(从头到脚带靴子,头盔、手套) - 2 Fire Axes 2 个消防斧头
- 2 Stainless knives ( for cutting seat belts) 2 吧不锈钢小刀 - 2 Hand lamps 2 把手灯 - 1 Crow bar 1 铁撬
- 1 Pair of cutting pliers 一副扁嘴钳子
- 1 Hack saw with spare blade 弓形锯子带备份刀口 - 1 Hammer 1 把锤子
- 1 Steel bar with a wedged tip 1 条带尖的钢棍
- 1 Pair of sheet metal shears
一副金属剪
Uncontrolled when printed
Last printed 19.10.2010 20:19 Page 3 of 16
6
Page 7 of 31
- 1 Bolt cutter 1断线钳子
- 1 Lightweight ladder (approx. 3 meter) 1 把重量轻的梯子(大约3米长) - 1 Jack for at least 0.5 ton 1 能顶起0.5吨的千斤顶
- 1 Metal hook with a shaft (approx. 3 meters) 一把带柄的金属钩(3米长)
Fire suits are located in the helideck reception office ( to be checked) 消防服装位于直升机机坪的接待办公室内(跟进核实)
Emergency equipment is located at aft entrance of helideck close to aft foam monitor and at starboard side close to starboard foam monitor
应急设备位于直升机机坪的入口处,靠近泡沫喷头的后面,启动控制板在靠近启动板泡沫喷头的一磅。
3.3.4 Additional fire fighting equipment ( min requirements , list to be updated to actual situation)辅助灭火设备(最低要求,清单根据实际情况进行更新)
-
3 CO2 extinguishers , 10kgs , with extension hose and nozzle able to reach helicopter engine intakes. A CO2 unit is located in close vicinity of each fire monitor.
3个10公斤二氧化碳的灭火瓶,带有延伸管线和喷嘴可以到达直升机发动机进气道。ACO2 灭火设备
位于每一个喷头的附近。
- 2 Fire hydrants with hose reels in vicinity of helideck. Located at starboard monitor - 2个消防栓带有圆盘管线位于直升机机坪启动喷头的附件。
3.3.5 Helicopter communication equipment 直升机通信设备
- 2 permanently installed aero mobile radio sets on the bridge, to listen in on two different frequencies simultaneously.
2套永久安装航空移动电台分布在梁桥上,同事可以监听两个不同的频率。
- 2 portable aero mobile radios, operated by the HLO during helicopter operations. - 2套可以手提的航空移动无线电,由直升机指挥员在直升机运行期间使用。
Wind, visibility as well as the vessel's movements put limits on helicopter operations. No helicopter operations shall take place if the wind force is or exceeds 60 knots. 风力、能见度、船的运行对直升机的运行造成限制。当风力风速超过60海哩,禁止直升机在本设施运行。 If the vessel's movements exceed the below-mentioned values, helicopter operations should be avoided. Such a decision shall be discussed in close consultation with the helicopter pilots.
如果船的运行动态超出下面提及的标准数值,禁止直升机运行。这样的决定应该咨询直升机飞行员。 4 Helicopter operation limitations and personnel organisation
直升机运行限制和人员结构
4.1 Helicopter Landing Limitations and Precautions
直升机着落限制和安全措施
Visual and Instrument Flight Regulations 能见运行和仪表运行规定
VFR and IFR Weather minimum - helicopter operations shall comply with local aviation regulations. However, where they are less conservative, the following apply to weather minimum.
能见和仪表天气标准-直升机运行必须遵守当地民航航空规章的要求。然而,如果当地的标准低于本程序标准,应该使用以下提供的天气标准。
7
Page 8 of 31
IFR Offshore approach minimum. 仪表海上进近天气标准
Conditions 条件 Cloud base 云高 Visibility Offshore Day 海上白天 Offshore Night海上夜间
Uncontrolled when printed 8
200' 300' Last printed 19.10.2010 20:19 能见度 800 m 1 200 m Page 4 of 16