Inductive Sensors
Inductive Sensors: Options E2/E4
Calibration Procedure
perform switch calibration while an area is known to be hazardous. When installing a Valvetop product with P&F NAMUR sensors, use of a commercially available switch tester like P&F part# ST0-03 is suggested.
Calibration may be performed using a 24Vdc power supply.
Step 1: With valve in the CLOSED position, disengage the BOTTOM cam from the splined hub and rotate clockwise until SW1 activates. Release cam to re-engage splined hub.
Step 2: Rotate valve to the OPEN position. Disengage the TOP cam from the splined hub and rotate counter-clockwise until SW2 activates. Release cam to re-engage the splined hub.
Step 3: Cycle valve CLOSED and OPEN several times to insure switches will maintain calibration.
For Reverse Acting actuators:
Step 1: With valve in the CLOSED position, disengage the TOP cam from the splined hub and rotate counter-clockwise until SW2 activates. Release cam to re-engage the splined hub.
Step 2: Rotate valve to the OPEN position. Disengage the BOTTOM cam from the splined hub and rotate clockwise until SW1 activates. Release cam to re-engage the splined hub.
Repeat Step 3 above.
*When using the (4) and (6) switch options, determine which switches are to indicate OPEN and which indicate CLOSED and then use the same calibration steps as above.
**Switches may also be set at midpoint, or any point, of travel for Dribble Control, or any other logic necessary for the application.
P & F NJ2-V3-N Switch Assembly
Switch Option E2
Switch Option E4
Switch Option E6
11