Do not touch connectors or pins on component boards. Do not touch circuit components inside the equipment. Use a static-safe workstation, if available.
Store the equipment in appropriate static-safe packaging when not in use.POINT I/O is grounded through the DIN rail to chassis ground. Use zinc plated yellow-chromate steel DIN rail to assure proper grounding. The use of other DIN rail materials (for example, aluminum, plastic) that can corrode, oxidize, or are poor conductors, can result in improper or intermittent grounding.
Secure DIN rail to mounting surface approximately every 200 mm (7.8 in.) and use end-anchors appropriately.
If this equipment is used in a manner not specified by the manufacturer, the protection provided by the equipment may be impaired.
ATTENTION
ATTENTION
ATTENTION
To comply with UL restrictions, field power and all connected devices must be powered from a single source compliant with the following:Class 2.
To comply with the CE Low Voltage Directive (LVD), field power and all connected I/O must be powered from a source compliant with the following:Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).