XT=ZT2- RT2=7.597 MΩ 相零阻抗:
RL-PE = RT=1.126 MΩ XL-PE = XT=7.597 MΩ ⑶ 母线和电缆的阻抗 每相阻抗:
Rwb=R*L=0.013x4=0.052MΩ Xwb=X*L=0.118x4=0.472MΩ 相零阻抗:
RL-PE =rL-PE L=0.039x4=0.156 MΩ XL-PE =xL-PE L=0.264x4=1.056 MΩ 计算K-5点的三相和单相短路电流 三相短路回路总阻抗:
R∑= Rs+ RT+ RWB=0.078+1.126+0.052=1.256 MΩ X∑= Xs+ XT+ XWB=0.780+7.597+0.472=8.849 MΩ 三相短路电流:
I
(3)
k
= Uc/3R∑+ X∑=25.84KA
22
短路电流冲击系数:
Kp=1+ e(-∏R∑/ X∑)=1.640 三相短路冲击电流:
i
(3)
p3
(3)
=2Kp IK=2*1.640*25.84=59.92KA
2
单相短路回路总相零阻抗:
R=0.052+1.126+0.156=1.334 MΩ X=0.520+7.597+1.056=9.173 MΩ 两相短路电流:
I
(2)
k2
=0.866x I
(2)
k
=0.866x25.84=22.38KA
单相短路电流:
I
(1)
k
=U/R+ X=24.91KA
22
20
计算K-7点的三相和单相短路电流 每相阻抗:
Rwb=R*L=0.013x11.2=0.146MΩ Xwb=X*L=0.118x11.2=1.322MΩ 相零阻抗:
RL-PE =rL-PE L=0.039x11.2=0.437 MΩ XL-PE =xL-PE L=0.264x11.2=2.957 MΩ 三相短路回路总阻抗:
R∑= 1.256+0.146=1.402 MΩ X∑= 8.849+7.597+1.322=10.171 MΩ 三相短路电流:
I
(3)
k
= Uc/3R∑+ X∑=22.49KA
22
短路电流冲击系数:
Kp=1+ e(-∏R∑/ X∑)=1.649 三相短路冲击电流:
i
(3)
p3
(3)
=2Kp IK=2*1.649*22.49=52.43KA
2
单相短路回路总相零阻抗:
R=1.334+0.437=1.771 MΩ X=9.173+2.957=12.130 MΩ 两相短路电流:
I
(2)
k2
=0.866x I
(2)
k
=0.866x22.49=19.48KA
单相短路电流:
I
(1)
k
=U/R+ X=18.84KA
22
变压器低压侧短路计算见表5-2。
21
表5-2 变压器低压短路计算
变压器T1低压侧短路计算 Un=380V 序号 元件 短路点 运行参数 R/mΩ X/mΩ Z/mΩ RL-PE/mΩ XL-PE/mΩ ZL-PE/mΩ Ik3\ kp ip3/kA Ik2/kA Ik1E/kA 1 2 SA T1 k-1 3 4 1+2 T1WB1 k-3 5 6 3+4 T1WB2 k-5 7 5+6 k-7 Skmax/MVA SrT/kVA 1250 r/mΩ/m 0.013 △Pk/kW 11 x/mΩ/m 0.118 204.00 Uk% 6 l/m 4 l/m 4 l/m 11.2 l/m 11.2 0.078 1.126 1.204 0.052 1.256 0.146 1.402 0.780 7.597 8.377 0.472 8.849 1.322 0.784 7.680 8.463 8.938 0.052 1.126 1.178 0.156 1.334 0.437 1.771 0.520 7.597 8.117 1.056 9.173 2.957 12.130 8.202 9.270 12.259 27.29 25.84 22.49 1.637 1.640 1.649 63.15 59.92 52.43 23.63 22.38 19.48 28.16 24.91 18.84 rL-PE/mΩ/m xL-PE/mΩ/m 0.039 r/mΩ/m 0.013 0.264 x/mΩ/m 0.118 rL-PE/mΩ/m xL-PE/mΩ/m 0.039 0.264 10.171 10.267
23
5.2.2 低压配电线路短路电流计算
共对四组配电干线进行了低压短路计算,分别是2层商店照明(W9)、4~7层照明(W13)、五层排烟风机(W25)、喷淋泵(W88)。短路计算见表5-3~表5-6。
表5-3 配电干线W9(AA4柜配出)低压短路计算
变压器T1低压侧配电干线W9(AA4柜配出)短路计算 Un=380V 序号 元件 短路点 运行参数 R/mΩ X/mΩ Z/mΩ RL-PE/mΩ XL-PE/mΩ ZL-PE/mΩ Ik3\ kp ip3/kA Ik2/kA Ik1E/kA 1 2 SA T1 k-1 3 T1WB1 4 5 1+2+3 W9 AA4 6 4+5 2AL1 Skmax/MVA SrT/kVA 1250 r/mΩ/m 0.013 △Pk/kW 11 x/mΩ/m 0.118 204.00 Uk% 6 l/m 9.6 l/m 9.6 l/m 30.8 l/m 30.8 0.078 1.126 0.125 1.329 0.650 0.780 7.597 1.133 9.510 5.900 0.784 7.680 9.603 0.052 1.126 0.374 1.553 34.742 36.295 0.520 7.597 2.534 10.653 5.883 16.534 10.764 39.884 24.05 14.32 1.645 1.057 55.93 21.39 20.83 12.40 21.46 5.79 rL-PE/mΩ/m xL-PE/mΩ/m 0.039 r/mΩ/m 0.31 0.264 x/mΩ/m 0.078 rL-PE/mΩ/m xL-PE/mΩ/m 1.128 0.191 10.877 11.913 16.131 24