Fig. 16.1 PID controller

What the PID controller is looking at is the difference (or “error”) between the PV and the SP. It looks at the absolute error and the rate of change of error. Absolute error means-is there a big difference in the PV and SP or a little difference? Rate of change of error means-is the difference between the PV or SP getting smaller or larger as time goes on.

When there is a “process upset”, meaning, when the process variable or the setpoint quickly changes-the PID controller has to quickly change the output to get the process variable back equal to the setpoint. [2] If you have a walk-in cooler with a PID controller and someone opens the door and walks in, the temperature (process variable) could rise very quickly. Therefore the PID controller has to increase the cooling (output) to compensate for this rise in temperature.

Once the PID controller has the process variable equal to the setpoint, a good PID controller will not vary the output. You want the output to be very steady (not changing) . If the valve (motor, or other control element) is constantly changing, instead of maintaining a constant value, this could cause more wear on the control element.

So there are these two contradictory goals. Fast response (fast change in output) when there is a “process upset”, but slow response (steady output) when the PV is close to the setpoint.

Note that the output often goes past (over shoots) the steady-state output to get the process back to the setpoint. For example, a cooler may normally have its cooling valve open 34% to maintain zero degrees (after the cooler has been closed up and the temperature settled down) . If someone opens the cooler, walks in, walks around to find something, then walks back out, and then closes the cooler door-the PID controller is freaking out because the temperature may have raised 20 degrees! So it may crank the cooling valve open to 50, 75, or even 100 percent-to hurry up and cool the cooler back down-before slowly closing the cooling valve back down to 34 percent. [3]

Let’s think about how to design a PID controller.

We focus on the difference (error) between the process variable (PV) and the setpoint (SP). There are three ways we can view the error.

This means how big is the difference between the PV and SP. If there is a small difference between the PV and the SP-then let’s make a small change in the output. If there is a large difference in the PV and SP-then let’s make a large change in the output. Absolute error is the “proportional” (P) component of the PID controller. The sum of errors over time

Give us a minute and we will show why simply looking at the absolute error (proportional) only is a problem. The sum of errors over time is important and is called the “integral” (I) component of the PID controller. Every time we run the PID algorithm we add the latest error to

搜索“diyifanwen.net”或“第一范文网”即可找到本站免费阅读全部范文。收藏本站方便下次阅读,第一范文网,提供最新高等教育PID控制器及智能控制英文文献(3)全文阅读和word下载服务。

PID控制器及智能控制英文文献(3).doc 将本文的Word文档下载到电脑,方便复制、编辑、收藏和打印
本文链接:https://www.diyifanwen.net/wenku/1176220.html(转载请注明文章来源)
热门推荐
Copyright © 2018-2022 第一范文网 版权所有 免责声明 | 联系我们
声明 :本网站尊重并保护知识产权,根据《信息网络传播权保护条例》,如果我们转载的作品侵犯了您的权利,请在一个月内通知我们,我们会及时删除。
客服QQ:xxxxxx 邮箱:xxxxxx@qq.com
渝ICP备2023013149号
Top